In air · Splash zone · Buried · Submerged
Four size charts, and how to read a code before you quote it
Place the end on the scale first: the band strikes out whole families, and a measured diameter only chooses between the codes left standing.
What is charted here, and what nobody publishes
Four charts are reproduced below as the manufacturer prints them: the GHSG gland taking a cable through an enclosure wall, the GAC cap closing an anode-to-lead-wire joint under backfill, the GEC L-PE cap that seals a duct-bound end and pulls on it, and the GSES seal holding curing pressure on a continuous-vulcanisation line. Two further ranges are published as spans only. Pole and pile caps have no per-size table at all — five sizes covering 140 to 460 mm (5.5 to 18.1 in), and finer rows would have to be invented.
Every heat-shrink part in these charts carries two internal diameters, and both have to be true. The supplied figure is a minimum, taken before the part has been heated, and must clear whatever you are pushing it over. The recovered figure is a maximum, taken after heating with nothing inside, and must sit below that same thing. A part whose recovered maximum exceeds your substrate has nowhere to go: it heats, stops short of contact, and the adhesive never wets the surface it was meant to.
Leave travel in hand. A jacket gone oval on a drum, a split pile top, an anode already carrying mastic — each is wider at one point than the mean you measured, and a code taken at the top of its published range has spent its recovery on the last few millimetres.
Worked, on the gland chart. Measure over the jacket where the gland mouth will finish: 26 mm. GHSG-3 is out, its range stopping at 25 mm. GHSG-4 takes it — supplied 39 mm slides on without forcing, recovered 19 mm sits 7 mm below the jacket, and that gap is the travel that drives adhesive into it. The code above fails for the opposite reason: GHSG-5 recovers to 35.5 mm at most, wider than the cable, so it can never touch it. A bigger part is not a safer part.
The notation, once, for every chart on this site
- D and d
- Two internal diameters on one part, not a diameter and a wall. D is the wide end, d the narrow end the lead wire leaves through. A chart carrying both describes a part that steps down.
- s — as supplied
- Out of the bag, expanded, never heated. Always quoted as a minimum: the part is at least this open.
- f — after free recovery
- Heated with nothing inside it. Always quoted as a maximum: left alone the part closes at least this far, and on a substrate it stops when it meets one.
- Ds, Df, ds, df
- The four combinations. Ds is the wide end supplied, Df the wide end recovered; ds and df are the same pair at the narrow end. Ds and Df are what you check a measurement against.
- Ta and Tw
- Recovered wall at the anode end and the wire end of a GAC cap, each ±10 per cent. A mechanical figure, not a fit figure — what the cap survives being knocked against during backfill.
- TL, La, Lw
- Total length of a GAC cap and its split between anode end and wire end. The two add to the total in every row, which is the check to run on a chart that reaches you scrambled.
- A and B
- On the gland chart, printed with no key. They scale with the part and are not internal diameters. Do not dimension an enclosure cut-out from them.
- Cable diameter range
- The manufacturer's own conclusion from the two diameters, and the column to quote from where it and your arithmetic disagree at a boundary.
Heat-shrinkable gland, GHSG-1 to GHSG-5
| Gala code | A | B | Supplied ID (min.) | Recovered ID (max.) | Cable diameter range |
|---|---|---|---|---|---|
| GHSG-1 | 70 | 25 | 13 | 4.3 | 5 – 103 |
| GHSG-2 | 70 | 25 | 19 | 5.5 | 6 – 17 |
| GHSG-3 | 95 | 35 | 29 | 12.5 | 14 – 25 |
| GHSG-4 | 116 | 51 | 39 | 19 | 20 – 37 |
| GHSG-5 | 178 | 89 | 70 | 35.5 | 37 – 67 |
Millimetres. The GHSG-1 row is printed as published and does not hold together: a range topping out at 103 mm cannot be served by a part supplied at 13 mm internal diameter. Treat GHSG-1 as the smallest code in the family and confirm its upper bound before quoting. The other four rows are internally consistent.
Anode cap, GAC 0420 to GAC 0550
| Code | Ds (min.) | Df (max.) | ds (min.) | df (max.) | TL set 1 | La set 1 | Lw set 1 | TL set 2 | La set 2 | Lw set 2 | Ta | Tw |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GAC 0420 | 41 | 20 | 13 | 4.5 | 120 | 55 | 65 | 135 | 65 | 70 | 3.5 | 2.5 |
| GAC 0420A | 50 | 20 | 14 | 4.5 | 115 | 55 | 60 | 135 | 63 | 70 | 3.5 | 2.5 |
| GAC 0540 | 82 | 40 | 16 | 5.0 | 150 | 85 | 65 | 180 | 116 | 64 | 4.7 | 3.7 |
| GAC 0540A | 108 | 40 | 16 | 5.0 | 140 | 80 | 60 | 180 | 116 | 64 | 4.8 | 3.8 |
| GAC 0550S | 108 | 50 | 20 | 5.5 | 180 | 90 | 90 | 250 | 140 | 110 | 4.7 | 3.9 |
| GAC 0550 | 145 | 50 | 20 | 5.5 | 175 | 90 | 85 | 250 | 140 | 110 | 4.7 | 3.9 |
Millimetres; lengths ±2 per cent, Ta and Tw ±10 per cent. The published key covers D, d, s, f, Ta and Tw and stops there — the two length groups carry no s or f marker, so their order is inferred from the diameter columns, not stated. La + Lw = TL holds within each group. Confirm which set is which against the manufacturer's anode cap page before dimensioning a drawing from it.
End cap with pulling eye, GEC 301L-PE to GEC 701L-PE
| Code no. | Ds (min.) | Df (max.) | Ls (min.) | Tf ±10% | Pulling strength (min.) | Cable range |
|---|---|---|---|---|---|---|
| GEC 301L-PE | 55 | 25 | 170 | 3.5 | 150 kg | 28 – 38 |
| GEC 401L-PE | 75 | 35 | 180 | 4.0 | 250 kg | 38 – 52 |
| GEC 501L-PE | 100 | 45 | 200 | 4.0 | 300 kg | 50 – 70 |
| GEC 601L-PE | 130 | 65 | 300 | 4.6 | 400 kg | 65 – 91 |
| GEC 701L-PE | 160 | 65 | 300 | 4.5 | 450 kg | 80 – 112 |
Millimetres, pulling strength as published in kilogrammes. The only chart of the four where a second figure can rule a code out after the diameter has ruled it in — the cable maker's own maximum pulling tension, and the lower of the two limits governs the draw. Ls is a supplied minimum length, Tf a recovered wall ±10 per cent; neither changes the fit. The part page is end cap with pulling eye.
Elastomeric CV-line end seal, GSES-1S and GSES-1
| Gala code | A | B | C | D | E | F | G | H |
|---|---|---|---|---|---|---|---|---|
| GSES-1S | 180 | 156 | 129 | 47 | 10 | 30° | 60° | 6 × 60° ⌀9 |
| GSES-1 | 255 | 226 | 195 | 68 | 10 | 30° | 60° | 6 × 60° ⌀9 |
A rubber sealing unit for the exit side of a CCV, VCV or SSCV line, not a cap fitted to a cut end — charted here because the plant engineer sizing one arrives on the same search. A to E are millimetres. F, G and H sit under the same heading and are not lengths: two angles and a hole pattern. The unit opens and closes hydraulically from the control panel, so A is the dimension that has to agree with the frame.
Three ranges published as spans, with no rows behind them
The Insulcap cable end cap runs GEC 001S to GEC 1101, covering cable from 2–4 mm at the smallest code to 230–460 mm at the largest. Its relief-valved variant runs GEC 102 RV to GEC 801 RV, 12 to 200 mm. Pole and pile caps are five sizes across 140 to 460 mm. None of the three is published code by code, and intermediate rows would be fabricated rather than reproduced, so none appears here. The spans are wide enough that the arithmetic above will not get you to a code on your own — send the diameter.
Questions that arrive with a measurement attached
Where exactly do I measure?
My diameter sits inside two codes. Which do I quote?
Is there a single end cap dimensions PDF?
Is there a size chart for the push-on PVC cap?
Does a chart tell me how wet the end can get?
The part behind each chart
- Cable gland entry sealsGHSG: what the three-part assembly does at an enclosure wall.
- Anode capsGAC: the buried lead-wire joint the chart above is sized for.
- End cap with pulling eyeGEC L-PE: the same five codes read as a pull decision.
- Insulcap cable end capsWhere the GEC 001S to GEC 1101 span lives.
- Pole capsThe five-size range with no chart, and how a crown diameter is taken instead.
- Gland datasheet (Gala Thermo Shrink)The manufacturer's own PDF behind the GHSG chart.
One diameter usually closes this out
A measurement over the jacket, pile top or anode body, plus the band the end will live in, is normally enough to name a code from the charts above. Open End is a reference site: the parts are made by Gala Thermo Shrink Pvt. Ltd. of Mumbai, and nothing here is stocked, priced or scheduled.